Panel Schedule Calculator
Assign circuits to a breaker panel, track load per phase, and check panel utilization. Add circuits with pole counts and loads to balance your panel before wiring.
- 100% free
- Phase balancing
- 1φ & 3φ panels
- Utilization check
Panel schedule
NEC 220.60 · Load balance
Formula
Load per phase = Σ circuit VA on phase
- Panel
- 1φ / 3φ
- Balance
- Phase A vs B
- Output
- VA per phase
- Check
- Utilization %
Panel configuration
Set up your panel and circuits
Circuits
Description
Poles
Breaker (A)
Load (VA)
Assumptions: circuits are assigned to alternating phases starting from slot 1. Multi-pole breakers (2P or 3P) apply their load to all phases they occupy. NEC 220.60 requires loads to be balanced between phases as far as practicable. This is a planning aid — always verify against the current NEC and your AHJ.
Panel schedule result
Load summary
Total connected load
50,200 VA (209.2 A)
- Panel rating
- 200 A @ 240 V = 48,000 VA
- Total connected VA
- 50,200 VA
- Total load amps
- 209.2 A
- Panel utilization
- 104.6%
- Total breaker rating
- 190 A
- Number of circuits
- 8
Load per phase
Safety & accuracy notice
This panel schedule calculator is a planning aid only. It is not engineering, a permit, or design approval, and it is not legal or code certification. Results are estimates based on the NEC standard method.
Always verify against the current adopted NEC (National Electrical Code), equipment listings and manufacturer instructions, and your local AHJ (Authority Having Jurisdiction — the inspector or department that enforces the code). Final panel schedules should be reviewed and approved by a licensed electrician or professional engineer.
Panel schedule FAQ
How do I balance loads across panel phases?
NEC 220.60 requires that the load be evenly distributed between phases as far as practicable. For single-phase panels, circuits alternate between Phase A and Phase B on adjacent poles. For three-phase panels, circuits rotate A-B-C. This calculator totals load per phase so you can see the balance.
How do I handle multi-pole breakers in a panel schedule?
A 2-pole breaker (e.g. 240 V range or dryer) contributes its full load to both Phase A and Phase B. A 3-pole breaker in a 3-phase panel contributes to all three phases. This tool lets you set the pole count per circuit so the load is assigned correctly.
Is this calculator a substitute for engineering?
No. It is a planning aid only — not engineering, a permit, or design approval. Always verify against the current adopted NEC and your local AHJ.
Related electrical tools
Next steps after scheduling your panel
Use the load totals to size your service, verify wire ampacity, and check voltage drop.
Calculate total service demand using NEC Article 220 standard method.
Wire size calculatorSize branch-circuit conductors against NEC ampacity and voltage drop.
Wire ampacity referenceLook up NEC Table 310.16 ampacity by wire size and insulation type.
Voltage drop calculatorCheck voltage drop on long branch circuit runs.
All free electrician toolsBrowse the full AceWatt calculator and template toolbox.
AceWatt plans & pricingSee the monthly plan path when the free tools are not enough.
Stop re-deriving NEC math on every job.
AceWatt CRM keeps your electrical takeoffs, quotes, scheduling, and customer history in one workflow built for contractors.
See AceWatt Plans & Pricing