Voltage Drop Calculator
Estimate single- and three-phase voltage drop in volts and percent using NEC Chapter 9 Table 8 conductor resistance. Enter the load, one-way run length, conductor size, and material to check your run against a voltage-drop limit before you pull wire.
- 100% free
- NEC-backed math
- Single & three-phase
- Instant volts + %
Voltage drop
NEC Chapter 9 · Table 8
Formula
Vd = k × R × I × L ÷ 1000
- Conductor
- Cu · Al
- Phase
- 1φ · 3φ
- Output
- Volts + %
- Check
- vs % limit
Circuit inputs
Describe the run
Assumptions: uncoated conductor resistance from NEC Chapter 9, Table 8 at 75°C; one-way run length (the tool doubles it for single-phase); steady-state resistive load; power factor of 1.0. Real circuits with reactance, elevated temperature, or low power factor may drop more.
Estimated result
Voltage drop
Voltage drop
7.72 V
- Voltage drop (percent)
- 3.22 %
- Voltage at load
- 232.28 V
- Conductor resistance R (copper, #12)
- 1.93 Ω / 1000 ft
- Phase multiplier (k)
- 2
Formula used
Vd = 2 × 1.93 × 20 × 100 ÷ 1000 = 7.72 V
Source: NEC Chapter 9, Table 8 (conductor DC resistance). Single-phase, 2-wire.
Safety & accuracy notice
This voltage drop calculator is a planning aid only. It is not engineering, a permit, or design approval, and it is not legal or code certification. Results are estimates that assume an ideal resistive load.
Always verify against the current adopted NEC (National Electrical Code), equipment listings and manufacturer instructions, and your local AHJ (Authority Having Jurisdiction — the inspector or department that enforces the code). Final circuit decisions should be reviewed and approved by a licensed electrician or professional engineer.
Voltage drop FAQ
What voltage drop is acceptable under the NEC?
The NEC recommends (in informational notes, not as a hard rule) a maximum of 3% voltage drop on a branch circuit or feeder, and no more than 5% total across both. Your AHJ or the equipment may require tighter limits. This tool defaults the comparison to 3%.
What formula does this calculator use?
Single-phase voltage drop is Vd = 2 × R × I × L ÷ 1000, and three-phase is Vd = √3 × R × I × L ÷ 1000, where R is the conductor resistance in ohms per 1000 ft (NEC Chapter 9, Table 8), I is the load in amps, and L is the one-way circuit length in feet.
Is this calculator a substitute for engineering?
No. It is a planning aid only — not engineering, a permit, or design approval. Always verify against the current adopted NEC and your local AHJ.
Related electrical tools
Next steps after checking voltage drop
Pair the voltage-drop check with conductor sizing and raceway fill, then bring the numbers into your quote.
Size the conductor against both ampacity and your voltage-drop limit.
Conduit fill calculatorCheck trade size against NEC Chapter 9 fill limits once conductors are picked.
Box fill calculatorEstimate required box volume for the conductors landing at a device.
CRM for electriciansTie field calculations to quotes, scheduling, and customer records.
All free electrician toolsBrowse the full AceWatt calculator and template toolbox.
AceWatt plans & pricingSee the monthly plan path when the free tools are not enough.
Stop re-deriving NEC math on every job.
AceWatt CRM keeps your electrical takeoffs, quotes, scheduling, and customer history in one workflow built for contractors.
See AceWatt Plans & Pricing